Closed Cooling Towers
Square Crossflow Closed Cooling Tower
In the KCH crossflow closed tower, the process fluid remains inside the coil while a separate spray-water loop is cooled through the fill and recirculated over the coil. Air crosses the fill and coil before being discharged by the fan.
Minimum order: 1 unit
Request a QuoteKey characteristics
- Closed process-fluid coil with a separate spray-water circuit and fill section.
- The catalogue shows an internal inspection passage and roof-mounted spray distribution for maintenance access.
- Fan, pump, coil and drift-collection components are arranged around the horizontal airflow path.
Typical fit
- Closed-loop systems that benefit from a crossflow tower arrangement.
- Consider for higher inlet temperatures or larger cooling ranges only after project-specific selection.
- Confirm foundation, lifting route and service access for the selected model before installation.
Selection basis
- Reference model KCH-25
- 25 m³/h process-water flow; 2 fans; spray-water flow 30 m³/h; L×W×H 2,800×1,840×2,180 mm.
- Catalog reference series
- KCH
- Reference table conditions
- Catalogue reference: atmospheric pressure 1.004×10⁵ Pa; dry bulb 31.5°C; wet bulb 28°C; standard inlet/outlet water 37°C / 32°C. Final selection depends on project conditions.